LARGEST STOCKHOLDER OF COPPER PIPE FITTINGS IN INDIA
Copper Pipe WEIGHT, DIMENSIONS CHART in mm, kg PDF Online
Copper Tube for Air Conditioning and Refrigeration (ACR) – Dimensions and Working Pressures as per ASTM B280 Standard
Copper tubes utilized in the ACR system are to conform to the ASTM B280 standard to allow for greater accuracy of dimensions and pressure handling capacity. These tubes provide outstanding corrosion protection and heat transfer capabilities for moving refrigerants in HVAC-R systems. They provide reliability and safety for cooling systems at specific working pressures made determined by the standard. This copper tube comes in different size and common in air conditioning and refrigeration system in both homes and industries.
Nominal Size (inches) | Annealed (A) or Drawn Temper (D) | Outside Diameter (inches) (mm) | Inside Diameter (inches) (mm) | Wall Thickness (inches)(mm) | Cross Sectional Area of Bore (square inches) |
---|---|---|---|---|---|
1/8 | A | 0.125 3.18 | 0.065 1.65 | 0.030 0.762 | 0.0033 |
3/16 | A | 0.187 4.75 | 0.128 3.25 | 0.030 0.762 | 0.0129 |
1/4 | A | 0.250 6.35 | 0.190 4.83 | 0.030 0.762 | 0.0284 |
5/16 | A | 0.312 7.92 | 0.248 6.3 | 0.032 0.813 | 0.0483 |
3/8 | A | 0.375 9.52 | 0.311 7.9 | 0.032 0.813 | 0.076 |
D | 0.375 9.52 | 0.315 8 | 0.030 0.762 | 0.078 | |
1/2 | A | 0.500 12.7 | 0.436 11.1 | 0.032 0.813 | 0.149 |
D | 0.500 12.7 | 0.430 10.9 | 0.035 0.889 | 0.145 | |
5/8 | A | 0.625 15.9 | 0.555 14.1 | 0.035 0.889 | 0.242 |
D | 0.625 15.9 | 0.545 13.8 | 0.040 1.02 | 0.233 | |
3/4 | A | 0.750 19 | 0.680 17.3 | 0.035 0.889 | 0.363 |
A | 0.750 19 | 0.666 16.9 | 0.042 1.07 | 0.348 | |
D | 0.750 19 | 0.666 16.9 | 0.042 1.07 | 0.348 | |
7/8 | A | 0.875 22.2 | 0.785 19.9 | 0.045 1.14 | 0.484 |
D | 0.875 22.2 | 0.785 19.9 | 0.045 1.14 | 0.484 | |
1 1/8 | A | 1.125 28.6 | 1.025 26 | 0.050 1.27 | 0.825 |
D | 1.125 28.6 | 1.025 26 | 0.050 1.27 | 0.825 | |
1 3/8 | A | 1.375 34.9 | 1.265 32.1 | 0.055 1.4 | 1.26 |
D | 1.375 34.9 | 1.265 32.1 | 0.055 1.4 | 1.26 |
Copper Tube and Pipe Weight & Dimensions Chart in mm, kg | Copper Pipe Weights for 12mm, 15mm, 22mm, 42mm
We, Kanchan Sales are one of the leading copper pipe fittings manufacturers in India offering an extensive collection of copper pipes and copper tube fittings for various uses. Copper pipes are used in the company and they enable the company to achieve the best results conforming to international quality standards. Here, we provide tabulated tables on the weight and size of copper tubes dependent on the nominal pipe sizes of 12mm, 15mm, 22mm, and 42mm and their corresponding nominal sizes in inches. Copper Pipe Charts These charts are useful for basic parameters such as outer diameter (OD), wall thickness (T) and weight per meter (kg/m) in order to identify the pipes that best fit your work.
12mm Copper Pipe Weight
The 12mm copper pipe, which is ½ inch nominal bore, is suitable products for small, strong demand applications like residential water supply, HVAC and miniature applications. This pipe presents very good flexibility and high resistance to corrosion. We have given accurate weight per meter and wall thickness for our 12mm copper pipes so that they can be installed easily and perform well.
Key Specifications:
- Nominal Size: ½ inch (12mm)
- Outer Diameter (OD): 12mm
- Wall Thickness (T): Standard thickness as per ASTM B88, ASTM B16.22
- Weight per Meter: X kg/m (adjust with actual data)
- Standard Length: 3 meters (10 feet) or 5.8 meters (20 feet)
15mm Copper Pipe Weight
The 15mm pipe is made of copper and has a ¾ inch nominal size and is well suited for use in commercial and residential buildings for hot and cold water distribution, conditioning and refrigeration and air conditioning. This pipe offers fine material strength and heat transfer rate. The weight chart of 15mm copper tube applies necessary information in your installations for you.
Key Specifications:
- Nominal Size: ¾ inch (15mm)
- Outer Diameter (OD): 15mm
- Wall Thickness (T): Standard thickness as per ASTM B88, ASTM B16.22
- Weight per Meter: X kg/m (adjust with actual data)
- Standard Length: 3 meters (10 feet) or 5.8 meters (20 feet)
22mm Copper Pipe Weight
The 22mm copper pipe commonly known as (7/8 inch nominal size pipeline diameter) is highly suitable for huge civil works and industries. Due to its designation it is used in systems that need higher flow, including central heating, fire protection systems as well as pipes for gas. Below is our 22mm copper pipe weight chart to help you with the perfect measuring and installation process for your systems.
Key Specifications:
- Nominal Size: 7/8 inch (22mm)
- Outer Diameter (OD): 22mm
- Wall Thickness (T): Standard thickness as per ASTM B88, ASTM B16.22
- Weight per Meter: X kg/m (adjust with actual data)
- Standard Length: 3 meters (10 feet) or 5.8 meters (20 feet)
42mm Copper Pipe Weight
The top copper piping diameter is at 42mm or 1 5/8 inch nominal size mainly for the higher capacity and Tough Duty construction. The most common applications are Industrial HVAC applications, water supply systems & fire suppression systems. It has been established that the enhanced performance and durability is due to the 42mm copper pipe. This sheet shows specifications of our 42mm copper pipe weight and we are confident this pipe is fit for large project.
Key Specifications:
- Nominal Size: 1 5/8 inch (42mm)
- Outer Diameter (OD): 42mm
- Wall Thickness (T): Standard thickness as per ASTM B88, ASTM B16.22
- Weight per Meter: X kg/m (adjust with actual data)
- Standard Length: 3 meters (10 feet) or 5.8 meters (20 feet)
BS 2871 Copper Tubes Table X, Y and Z – Working Pressures vs. BS 2871 Copper Tubes Table X, Y and Z – Working Size
The BS 2871 standard Copper Tubes in Tables X, Y and Z state the working pressures and the related working sizes. Table X is for Type I tubes generally used in domestic water system, heating purpose etc. Table Y deals with Type 2 tubes suited for air conditioning and refrigeration applications. Table Z present the Type 3 tubes which are designed for the industrial like systems. Every table offers the maximum safe pressures and the necessary tubing sizes to guarantee that the copper tubes are right for their specific use and have the right pressure capabilities required by safety and efficiency.
Nom. Diameter (mm) | Outside Diameter (mm) | Table X Half hard light gauge tube | Table Y Half hard an annealed tube | Table Z Hard drawn thin wall tube | |||
---|---|---|---|---|---|---|---|
Thickness (mm) | Maximum Working Pressure (N/mm2) | Thickness (mm) | Maximum Working Pressure (N/mm2) | Thickness (mm) | Maximum Working Pressure (N/mm2) | ||
6 | 6 | 0.6 | 13.3 | 0.8 | 14.4 | 0.5 | 11.3 |
8 | 8 | 0.6 | 9.7 | 0.8 | 10.5 | 0.5 | 9.8 |
10 | 10 | 0.6 | 7.7 | 0.8 | 8.2 | 0.5 | 7.8 |
12 | 12 | 0.6 | 6.3 | 0.8 | 6.7 | 0.5 | 6.4 |
15 | 15 | 0.7 | 5.8 | 1 | 6.7 | 0.5 | 5 |
18 | 18 | 0.8 | 5.6 | 1 | 5.5 | 0.6 | 5 |
22 | 22 | 0.9 | 5.1 | 1.2 | 5.7 | 0.6 | 4.1 |
28 | 28 | 0.9 | 4 | 1.2 | 4.2 | 0.6 | 3.2 |
35 | 35 | 1.2 | 4.2 | 1.5 | 4.1 | 0.7 | 3 |
42 | 42 | 1.2 | 3.5 | 1.5 | 3.4 | 0.8 | 2.8 |
54 | 54 | 1.2 | 2.7 | 2 | 3.6 | 0.9 | 2.5 |
67 | 67 | 1.2 | 2 | 2 | 2.8 | 1 | 2 |
76.1 | 76.2 | 1.5 | 2.4 | 2 | 2.5 | 1.2 | 1.9 |
108 | 108.1 | 1.5 | 1.7 | 2.5 | 2.2 | 1.2 | 1.7 |
133 | 133.4 | 1.5 | 1.4 | 1.5 | 1.6 | ||
159 | 159.4 | 2 | 1.5 | 1.5 | 1.5 |
Copper Pipe and Tubes – Type K
K copper pipe type is much renowned for its largely thickness of the pipe walls and therefore tend to possess great stand on pressures exerted allowing their use in dwelling as well as working stations. These pipes are usually applied wherever high pressure is exerted and meet the necessary requirements of the industry as for the quality and safety.
Nominal Size – Tube Outside Diameter(mm) | Wall Thickness (mm) | Tolerance +/- (mm) | Weight (kg/m) |
6 | 0.9 | 0.08 | 0.12 |
8 | 0.9 | 0.09 | 0.18 |
10 | 0.9 | 0.09 | 0.23 |
12 | 1.2 | 0.1 | 0.36 |
15 | 1.2 | 0.1 | 0.47 |
18 | 1.2 | 0.1 | 0.57 |
22 | 1.6 | 0.15 | 0.92 |
28 | 1.6 | 0.15 | 1.19 |
35 | 1.6 | 0.15 | 1.50 |
42 | 1.8 | 0.2 | 2.03 |
54 | 2.1 | 0.2 | 3.06 |
67 | 2.4 | 0.25 | 4.35 |
79 | 2.8 | 0.3 | 5.99 |
105 | 3.4 | 0.35 | 9.70 |
130 | 4.0 | 0.4 | 14.2 |
156 | 4.8 | 0.5 | 20.3 |
206 | 6.8 | 0.7 | 38.0 |
257 | 8.5 | 0.85 | 59.3 |
308 | 10.3 | 1 | 86.1 |
Copper Pipe and Tubes – Type L
Type L copper pipes are medium thickness pipes having higher strength than thin walled pipes but not as high as that of the thick walled pipes and therefore they are used in residential and small commercial buildings. To give good service and strength they are popularly applicable in water and heating pipeline systems.
Nominal Size – Tube Outside Diameter(mm) | Wall Thickness (mm) | Tolerance +/- (mm) | Weight (kg/m) |
6 | 0.7 | 0.07 | 0.10 |
8 | 0.8 | 0.08 | 0.16 |
10 | 0.8 | 0.08 | 0.21 |
12 | 0.9 | 0.09 | 0.28 |
15 | 1.0 | 0.1 | 0.39 |
18 | 1.0 | 0.1 | 0.48 |
22 | 1.1 | 0.1 | 0.65 |
28 | 1.2 | 0.1 | 0.90 |
35 | 1.4 | 0.15 | 1.32 |
42 | 1.5 | 0.15 | 1.71 |
54 | 1.7 | 0.15 | 2.50 |
67 | 2.0 | 0.15 | 3.65 |
79 | 2.3 | 0.2 | 4.95 |
105 | 2.8 | 0.25 | 8.04 |
130 | 3.1 | 0.3 | 11.0 |
156 | 3.5 | 0.3 | 15.0 |
206 | 5.0 | 0.35 | 28.2 |
257 | 6.3 | 0.5 | 44.4 |
308 | 7.1 | 0.65 | 60.0 |
Copper Pipe and Tubes – Type M
Thin wall thickness in Type M copper pipes makes them suitable for low pressure actions such as plumbings and heating in homes. They are affordable and are used mostly in water supply and air ventilations, providing standard performance for normal usage.
Nominal Size – Tube Outside Diameter(mm) | Wall Thickness (mm) | Tolerance +/- (mm) | Weight (kg/m) |
6 | 0.6 | – | 0.09 |
8 | 0.6 | – | 0.13 |
10 | 0.6 | – | 0.16 |
12 | 0.6 | 0.06 | 0.19 |
15 | 0.7 | 0.07 | 0.28 |
18 | 0.7 | 0.07 | 0.34 |
22 | 0.8 | 0.08 | 0.48 |
28 | 0.9 | 0.09 | 0.69 |
35 | 1.1 | 0.1 | 1.05 |
42 | 1.2 | 0.1 | 1.37 |
54 | 1.5 | 0.15 | 2.21 |
67 | 1.6 | 0.15 | 2.94 |
79 | 1.8 | 0.2 | 3.90 |
105 | 2.4 | 0.25 | 6.92 |
130 | 2.7 | 0.25 | 9.65 |
156 | 3.1 | 0.3 | 13.3 |
206 | 4.3 | 0.45 | 24.4 |
257 | 5.4 | 0.55 | 38.2 |
308 | 6.4 | 0.65 | 54.2 |
BS EN 13348 Medical Grade Pipe (Typically available dimensions in ready)
The BS EN 13348 Medical Grade Pipe standard focuses on the copper pipes used for Medical gas systems because, those pipes must have high purity and anticorrosive qualities. These pipes are used in hospitals and healthcare establishments for transport of such media as medical oxygen, medical nitrogen, nitrous oxide, and air, subjecting to critical environmental standards for sterility, safety, and dependability within clinical applications.
Nominal Outside Diameter (mm) | Tube Length (m) | Wall Thickness (mm) |
---|---|---|
12 | 6 | 0.6 |
15 | 3, 6 | 0.7 |
22 | 3, 6 | 0.9 |
28 | 3, 6 | 0.9 |
35 | 6 | 1.0 |
42 | 6 | 1.0 |
54 | 6 | 1.0 |
67 | 6 | 1.5 |
76 | 6 | 1.5 |
108 | 6 | 1.5 |
133 | 6 | 1.5 |
159 | 6 | 2.0 |
219 | 6 | 3.0 |
BS EN 13348 Medical Grade Pipe (Typical Temper of Material Required as per Standard)
The BS EN 13348 provides the requirements for the specification of copper pipes which qualifies them for use in the medical gas pipeline. These pipes are made with specifications of high purity, excellent corrosion resistance and high hygiene to comprise safe and efficient means of transport of such medical gases as oxygen, nitrous oxide and medical air. The BS EN 13348 pipes are widely popular in the healthcare centers such as hospitals, clinics and other related healthcare sectors to deliver long lasting solutions for medical industry.
Material Temper | Tensile Strength | Elongation min. | Vickers Hardness | |
---|---|---|---|---|
Designation | Commonly used term | (MPa) | (%) | HV5 |
R250 | half hard | 250 | 30, 20 | 75 – 100 |
R290 | hard | 290 | 3 | over 100 |
Copper Tube for Air Conditioning and Refrigeration (ACR) Working Pressures as per ASTM B280 Standard specs
The ASTM B280 standard features the dimensions, chemical and mechanical properties as well as working pressure of copper tubes intended for use in ACR systems. These copper tubes are manufactured to the contingent working pressure for HVAC and refrigeration applications without compromising the flow rates.
Nominal Size (inches) | Max. Working Pressure (psi) | ||
---|---|---|---|
Annealed Coils | Annealed Straight Lengths | Drawn Straight Lengths | |
1/8 | 2613 | ||
3/16 | 1645 | ||
1/4 | 1195 | ||
5/19 | 1017 | ||
3/8 | 836 | 777 | 1524 |
1/2 | 618 | 664 | 1302 |
5/8 | 525 | 615 | 1206 |
3/4 | 435 | 538 | 1055 |
7/8 | 495 | 496 | 972 |
1 1/8 | 420 | 421 | 825 |
1 3/8 | 373 | 374 | 733 |
1 5/8 | 347 | 348 | 682 |
2 1/8 | 309 | 607 | |
2 5/8 | 286 | 560 | |
3 1/8 | 270 | 529 | |
3 5/8 | 258 | 506 | |
4 1/8 | 249 | 489 |
Weight of All types of Copper Pipes and Tubes in inches and mm with the working pressure specified in kg and lbs:
- 12mm Copper Pipe Weight
- 15mm Copper Pipe Weight
- 22mm Copper Pipe Weight
- 42mm Copper Pipe Weight
- 1/4″ Copper Tube Weight (6mm Copper Coil Weight Information)
- 5/16″ Copper Tube Weight (8mm Copper Coil Weight Information)
- 3/8″ Copper Tube Weight (10mm Copper Coil Weight Information)
- 1/2″ Copper Tube Weight (12mm Copper Coil Weight Information)